304GCX SelecTone® Hazardous Location Audible Signaling Device
- Available in 24VDC
- Reliable, solid-state circuitry
- Built-in gain control
- Digital signal amplification
- Fused input and output
- Type 4X enclosure
- External mounting tabs
- 4-wire supervisable power circuit
- UL Listed and CSFM Approved

Federal Signal Models 304GCX and 314GCX Hazardous Location Amplified Speakers are designed to produce crisp, clear tones in supervised alarm notification systems. Both speakers amplifiers are compatible with fire alarm, voice evacuation, suppression supervised control panels and power boosters.
These amplified speakers can broadcast tones generated by a Tone Card installed into the speaker (the plug-in 32-tone UTM) or by a central tone source in a voice evacuation or paging system. When live public address or voice messages are required, plug-in Connector Cards (AM25CK or AM70CK) interface with the audio output of the EVAC panel.
The speaker cone and projector are constructed of rugged spun aluminum. The solid-state amplifier circuit is protected in a diecast aluminum housing. Dust and moisture-proof gaskets provide protection from the elements. All external surfaces are sealed with gray powder coat paint. The 304GCX and 314GCX are easily installed with external mounting tabs.
The 304GCX and 314GCX are UL Listed for Class I, Division 2, Groups A, B, C and D; Class II, Division 2, Groups F and G; and Class III.
The rugged construction and high output of the Model 304GCX and 314GCX make it ideal for use in harsh environments with high ambient noise levels. Both models feature an internal gain control for adjustment to suit area.
Special Considerations
- Tone Card (UTM)
- Specify Connector Kit for use in systems
Models
Part # | Description | Ship Weight | Net Weight | |
---|---|---|---|---|
304GCX-024 | SelecTone, 24VDC, Div 2, hazardous location | 5.7 lbs. | 4.5 lbs. | Add to Quote > |
Accessories
Part # | Description | Ship Weight | |
---|---|---|---|
NOT APPLICABLE |
Replacement Parts
Description | Part # | |
---|---|---|
Amplifier Assembly | K2005356A | Add to Quote > |
Voice Coil, Series B | K8593035A | Add to Quote > |
Speaker Assembly | K8593082A | Add to Quote > |
Connector, 4-Position | K140340B | Add to Quote > |
Agency
Listed By Underwriter's Laboratory (ULus) | |
---|---|
Audible signal devices for use in hazardous locations | UGKZ_E12629.pdf |
Audible signal appliances | ULSZ_E4813.pdf |
Listed By California State Fire Marshall (CSFM) | |
---|---|
Misc. devices/control unit accessories | 7135_0811_003.pdf |
Specs
Voltage | 24VDC |
---|---|
Mount | Surface |
Operating Current | 0.7 Amps |
Operating Temperature Min. | -40 F |
Operating Temperature Max. | 150 F |
Decibels per UL1480 | 95 at 10 Feet 105 at 1 Meter |
Decibels on Axis | 108 at 10 Feet 118 at 1 Meter |
Standby Current | 0.15 Amps |
Enclosure Rating | Type 4X |
Height | 12.4 IN |
Width | 7.9 IN |