Federal Signal

- Safety and Security Systems / Industrial request quote contact us Call Us Toll-Free: 877.268.3700

Initiating

WCP-TR ATEX Call Point-Tool Reset

  • Zone 1, 2, 21 and 22 hazardous area approved
  • Works as a control for fire and gas alarm systems
  • Spring loaded cover protects push button
  • Requires two-action activation
  • Manufactured from corrosion proof, marine grade, copper free LM6 aluminum
  • Certified to ATEX and IECEx Standards

Model WCP-TR push button, tool resettable manual call points are approved for Zone 1, 2, 21 and 22 hazardous areas for the control of fire and gas alarm systems. Available with and without monitoring resistors all versions are certified to ATEX and IECEx standards.

The push button mechanism is protected by a spring loaded cover therefore the switch requires a two-action activation. The push button is user resettable via the use of the special key supplied with the unit.

The WCP-TR features enclosures manufactured from corrosion proof, marine grade, copper free LM6 (A413) aluminium which is phosphated and powder coated.

Special Considerations

  • NOTE: "XXX" is a placeholder for end-of-line and/or series resistor that must be included at time of order.
  • Consult Page 2 of Data Sheet: WCP-PB

Models

Part # Description Ship Weight Net Weight  
WCP-TR-S BEx CP3 A/B push button call point, red, std terminals 1.98 lbs. 1.76 lbs. Add to Quote >
WCP-TR-SL BEx CP3 A/B push button call point, red, std terminals, duty label 1.98 lbs. 1.76 lbs. Add to Quote >
WCP-TR-D  BEx CP3 A/B push button call point, red, DIN rail terminals 1.98 lbs. 1.76 lbs. Add to Quote >
WCP-TR-DL BEx CP3 A/B push button call point, red, DIN rail terminals, duty label 1.98 lbs. 1.76 lbs. Add to Quote >
WCP-TR-S-xxx BEx CP3 A/B push button call point, red, std terminals, Req: sys voltage, EOL resistor, series resistor 1.98 lbs. 1.76 lbs. Add to Quote >
WCP-TR-SL-xxx BEx CP3 A/B push button call point, red, std terminals, duty label, Req: sys voltage, EOL resistor, series resistor 1.98 lbs. 1.76 lbs. Add to Quote >
WCP-TR-D-xxx BEx CP3 A/B push button call point, red, DIN rail terminals, Req: sys voltage, EOL resistor, series resistor 1.98 lbs. 1.76 lbs. Add to Quote >
WCP-TR-DL-xxx BEx CP3 A/B push button call point, red, DIN rail terminals, duty label, Req: sys voltage, EOL resistor, series resistor 1.98 lbs. 1.76 lbs. Add to Quote >

Accessories

Part # Description Ship Weight  
NOT APPLICABLE

Replacement Parts

Description Part #  
Tool reset KAK15095001 Add to Quote >

Agency

ATEX Certificate
Sira - Manual Call Point Sira_10ATEX3103X.pdf
IECEx Certificate of Conformity
Certification Scheme for Explosive Atmospheres IECEx_SIR_10_0047X.pdf

Diagrams

NO DIAGRAM AVAILABLE

Specs

WCP-TR
Voltage

250VAC Max., Switch Rating 5.0A Max.

50VDC Max., Switch Rating 1.0A Max.

Monitoring Resistors No
Terminals 6 x 4mm²
ATEX / IECEx Ratings

II 2G Ex e d IIC T6 Gb

II 2D Ex t IIIC T60ºC Db

Ingress Protection (IP) IP66
Ambient Temperature Min. -40 F
Ambient Temperature Max. 131 F
WCP-TR-XXX
Voltage 56VDC Max., Rating <50V 1.0A, >50V 0.75A
Monitoring Resistors Yes
Terminals 6 x 4mm² or 8 x 2.5mm² DIN rail
ATEX / IECEx Ratings

II 2G Ex e d mb IIC T4 Gb

II 2D Ex t IIIC T75ºC Db

Ingress Protection (IP) IP66
Ambient Temperature Min. -40 F
Ambient Temperature Max. 122 F
GENERAL
Housing Material Marine grade copper free LM6 Aluminium
Housing Finish Phosphated and powder coated finish: anti-corrosion
Product Color RAL3000 Red (others available on request)
Cable Entries 2 x M20 clearance top and 1 x M20 clearance side. Back box can be rotated to give 2 x bottom and 1 x side entries.
Stopping Plugs 2 x Exe nylon plugs as standard, brass and stainless steel plugs optional
Optional DIN Rail Terminal Blocks 8 x 2.5mm
Optional Duty Label Metalized polyester
Federal Signal distributed by Gross Automation - Brookfield, WI - Phone: (262) 252-1600 - Fax: (262) 252-1616